Analisa Pola Sambaran Petir Pada Jaringan Transmisi Untuk Meningkatkan Keandalan Penyaluran Pada Sutt 150 Kv Jatirangon–Cibubur
DOI:
https://doi.org/10.35968/jti.v13i2.2267Abstract
This study aims to analyze the shielding angle of the ground wire against the phase conductor and the lightning impulse voltage on the 150 kV Jatirangon–Cibubur transmission line to identify the causes of disturbances and determine mitigation measures to improve transmission reliability. The research method uses historical lightning strike data from the FALLS application for the 2013–2024 period, disturbance data from the FOIS application, tower construction dimension measurements from 2024, and tower grounding measurements from 2023. The analysis was conducted by calculating the shielding angle using the Electro Geometric Model (EGM) and evaluating lightning impulse voltage using surge impedance calculation. The results show that several towers have shielding angles exceeding 15 degrees and therefore do not comply with SPLN T5.014-1:2021, namely circuit #1 phase R T.6, T.8, T.10, T.12, T.14, T.15 and circuit #2 phase R T.9, T.10, T.15, T.18, T.20. All suspension-type towers have the potential for back flashover (BFO) because the lightning impulse voltage exceeds the installed insulator BIL. In conclusion, mitigation can be performed by modifying the tower traverses to meet the shielding angle standard and replacing the insulators with higher BIL values.Downloads
Published
2026-11-29
How to Cite
Nopi, B. D. S., Yulianti, B., & Haryanti, M. . (2026). Analisa Pola Sambaran Petir Pada Jaringan Transmisi Untuk Meningkatkan Keandalan Penyaluran Pada Sutt 150 Kv Jatirangon–Cibubur. JURNAL TEKNOLOGI INDUSTRI, 13(2), 75–83. https://doi.org/10.35968/jti.v13i2.2267
Issue
Section
Artikel
License
Copyright (c) 2026 Bagus Dewok Saputra Nopi, Bekti Yulianti, Munnik Haryanti

This work is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License.